The following Zone Schedule is an example of the 'as fitted' zone schedule which will be found on the 'as fitted' wiring diagram. It is to be used in conjunction with the CAD pipe layout drawing. You will see that it exactly ties up with the sequence of the individual pipe circuits 'as fitted' back to the manifold(s). For ease of understanding, the sequence of the controllable areas are numbered from left to right on the manifold(s). Below the exampled zone schedule, there is a brief description of each of the headings. The most important piece of information that the zone schedule gives is which channel number to set each room sensor to. This is normally done at the commissioning stage.
| ZONE SCHEDULE | |||||
|---|---|---|---|---|---|
| ROOM NAME | OUTPUT NUMBER | MODULE TYPE | SENSOR TYPE | SET TO CHANNEL | USE |
| 1 | WLM 2FS | WLTA | 1 | 1 ACTUATOR | |
| 2 | WLM 2FS | WLCT | 2 | 2 ACTUATOR | |
| 3 | WLM 2FS | WLTD | 3 | ||
| 4 | WLM 2FS | WLCT | 4 | ||
| 5 | WLM 2FS | WLTA | 5 | ||
| 6 | WLM 2FS | WLTA | 6 | ||
| 7 | WLM 2FS | WLTD | 7 | ||
| 8 | WLM 2FS | WLCT | 8 | ||
| 9 | 2 WLM 1AO | WLTA | 9 | ||
| 10 | 2 WLM 1AO | WLTA | 10 | ||
| 11 | 2 WLM 1AO | WLTD | 11 | ||
| 12 | 2 WLM 1AO | WLTA | 12 | ||
| 13 | 2 WLM 1AO | WLTA | 13 | ||
| 14 | 2 WLM 1AO | WLTA | 14 | ||
ROOM NAME - Description of the room allocated to that output.
OUTPUT NUMBER - Relates to the output number serving the thermal actuator(s).
MODULE TYPE - Describes which module the output comes from.
SENSOR TYPE - Describes what type of sensor is allocated to that room.
SET TO CHANNEL - Instructs what channel number to set inside the sensor.
USE - States how many actuators are connected to that output.
Points to note: